Two weeks after construction was completed on Kirkwood Mountain Club, one of main boilers exploded.  KMC claimed that the main gas pressure regulator installed by California Hydronics caused the explosion by letting gas into the boiler at too high of a pressure.

We inspected & test both an exemplar regulator and the incident regulator and determined that they functioned properly when installed properly.  We also determined that the actual origin of the explosion was not the boiler; instead it was in the exhaust flue.  Finally, we determined that the variation in pressure to the boiler was in the control system between the regulator and the boiler.

photo1 photo2 test report